PACKAGESTANDBYSYSTEMSINSTALLATION ANDOPERATIONS MANUALPSS21/ADSE 7110
Page 80210-10 REV B60706-197 Depending on the distance, 14 to 16 gauge stranded wire shouldbe used. It is suggested that these wires be labeled S1 an
60706-197Page 90210-10 REV BASCO 165 UL SWITCHYour DC connection points in the ASCO 165 ATS areterminals “4” and “5 on the interface terminal block.AS
Page 100210-10 REV B60706-197DSE 7110 CONTROLLERA. MENU NAVIGATION BUTTONS – Left and Right buttons selectdifferent grouping (i.e. Engine reading Gene
60706-197Page 110210-10 REV BSTARTING PROCEDUREMANUAL MODE********************* WARNING *********************EQUIPMENT DAMAGE - BEFORE ATTEMPTING TO
Page 120210-10 REV B60706-197TROUBLESHOOTING TABLESUNIT WILL NOT CRANK WHEN THE POWER FAILS1. DSE Controller not in "AUTO".2. Transfer contr
60706-197Page 130210-10 REV BVOLTAGE REGULATOR WIRINGTHREE PHASE AND SINGLE PHASE
Page 140210-10 REV B60706-197THREE PHASE AC WIRINGHIGH AND LOW WYETHREE PHASE-LOW WYE120/208 VOLTSTHREE PHASE-HIGH WYE277/480 VOLTS
60706-197Page 150210-10 REV BTHREE PHASE AC WIRING - DELTASINGLE PHASE AC WIRINGSINGLE PHASE120/240 VOLTSTHREE PHASE -DELTA120/240 VOLTS
Page 160210-10 REV B60706-197ENGINECONTROLSCHEMATIC
60706-197Page 170210-10 REV BPSS21 OUTLINE DRAWING AND WIRING ENTRANCEDIMENSIONS ARE SUBJECT TO CHANGE. ALWAYS OBTAIN ACERTIFIED DRAWING FOR CONSTRUC
Page iTABLE OF CONTENTSINTRODUCTION iGUIDE TO PRODUCT SAFETY 1BASIC INFORMATION 2Description 2DSE 7110 Description 3Specification Table 3PREPARING
Page 180210-10 REV B60706-197MODE ICONSAUTO RUN ICONSINSTRUMENTATION ICONS
60706-197Page 190210-10 REV BWARNING ALARMS
Page 200210-10 REV B60706-197SHUTDOWN ALARMS
60706-197Page 210210-10 REV BACCESSING THE FRONT PANELCONFIGURATIONEDITING A PARAMETER
60706-197- 0210-00WINCO, Incorporated warrants to the original purchaser for 12 months or 1000 hours whichever occurs first, that goods manufactured
60706-197Page 10210-10 REV B2. FIRE HAZARD - Natural gas and L.P. present a hazard ofpossible explosion and/or fire.a. Do not smoke or use open flame
Page 20210-10 REV B60706-197TESTING POLICY:Before any generator is shipped from the factory, it is fullychecked for performance. The generator is loa
60706-197Page 30210-10 REV BSPECIFICATIONSGENERATORMODEL WATTS VOLTS AMP HZ PH RPMPSS21-3 21,000 120/240 89.0* 60 1 1800PSS21-4 22,000 120/208 76.4**
Page 40210-10 REV B60706-197**** CAUTION ****EQUIPMENT DAMAGE - These units must be mounted on asolid concrete pad to prevent air from exiting under
60706-197Page 50210-10 REV BLP LIQUID WITHDRAWAL SYSTEMSWhen installing a unit equipped the LP liquid withdrawal aprimary regulator is not required on
Page 60210-10 REV B60706-197CAUTION – PERSONAL DANGERCAUTION - NEVER dispose of a battery in a fire. The battery iscapable of exploding.CAUTION - DO N
60706-197Page 70210-10 REV BTo wire the automatic transfer switch into the existing wiring, firstdetermine which circuits will be on the emergency loa