PACKAGEDSTANDBYSYSTEMPSS25000/AAutomatic TransferSwitchPSS25000/AEngine GeneratorP/N 60706-171-5076-10INSTALLATION AND OPERATORS MANUAL
PAGE 860706-1715076-10The Automatic Transfer Switch connects the load (lights,furnace, outlets, etc.) to the normal power line duringstandby. When no
PAGE 95076-10 60706-171side contactor, terminals G1 and G3. The G-N connectionwill be made on the stand-off in the bottom of the ATS.The line termina
PAGE 1060706-1715076-10NOTE:Code requires a fuse disconnect (circuit breaker) beinstalled in the incoming power line wiring directly in frontof the A.
PAGE 115076-10 60706-171ASCO 300 UL SWITCHYour DC connection points in the ASCO 300 ATS areterminals “14” and “15”. Depending on the size of theswitc
PAGE 1260706-1715076-10F Proper fuel line material, and size.F All fuel line connections tight.F Fuel line protected and a moisture trap installed(may
PAGE 135076-10 60706-1718. Defective start solenoid.9. Defective remote start solenoid.10. Locked up engine generator set.ENGINE CRANKS BUT WILL NOT S
PAGE 1460706-1715076-10110/60ATS-3/C230/150ATS-3/CNON-UL ATS SCHEMATIC230/150ATS-4/D230/150ATS-17/DNON-UL ATS SCHEMATICLEGENDLTS Line Side Contactor G
PAGE 155076-10 60706-171WINCO/ZENITH UL ATSComplete installation instructions for WINCO/ZENITH UL Automatic Transfer Switches are con-tained in the op
PAGE 1660706-1715076-10ASCO 165 UL ATSComplete installation instructions for the ASCO 165 UL Automatic Transfer Switches are con-tained in the operato
PAGE 175076-10 60706-171PSS25000 LAYOUTNON-UL ATS PANELOUTLINE DIMENSIONSATS SIZE REF A REF B REF C REF D REF E110/60 ATS 17.00” 8.00” 8.10” 20.00” 1
Read and understand all instructions in themanual before starting and operating thegenerator set.USING THIS MANUALCongratulations on your choice of a
PAGE 1860706-1715076-10PSS25000 DC SCHEMATIC
PAGE 195076-10 60706-171PSS25000 AC SCHEMATIC120/208 VOLT THREE PHASE277/480 VOLT THREE PHASE
PAGE 2060706-1715076-10120/240 VOLT SINGLE PHASE120/240 VOLT THREE PHASEPSS25000 AC SCHEMATIC
MAINTENANCE LOGDATE ITEMWORK PERFORMED
225 SOUTH CORDOVALE CENTER, MN 56057507-357-6821P/N 60706-171 5079-10WINCO, Incorporated warrants to the original purchaser for 12 months that goods
PAGE 15076-10 60706-171SAFETY INFORMATIONThis engine generator set has been designed andmanufactured to allow safe, reliable performance.Poor maintena
PAGE 260706-1715076-10TESTING POLICY:Before any generator is shipped from the factory, it isfully checked for performance. The generator is loadedto
PAGE 35076-10 60706-171SPECIFICATIONSGENERATORMODEL WATTS* VOLTS Pf AMPS* HZ pH RPMPSS25000 25,000 120/240 1.0 104.0 60 1 3600PSS25000-4 25,000 120/
PAGE 460706-1715076-10INSTALLATIONGeneral Information ****************** WARNING **** *************Before proceeding with the installation, be s
PAGE 55076-10 60706-171also true for the single dual stage regulators, they shouldalso be minimum of 10 feet from the unit. If this is notdone the d
PAGE 660706-1715076-10Natural Gas1 3 4UNIT OFF LINE PSI 7-11 in 7-11 in4-6 oz. 4-6 oz.STARTING LINE PSI 7-11 in 7-11 in4-6 oz. 4-6 oz.NO LOAD
PAGE 75076-10 60706-1716. If the pressure is correct, remove the meter andreinstall the pipe plug. Next remove the 1/8 inch NPT plugon the carburetor